首页  科学研究  学术论文  2023年
 
Experimental research on the thermal characteristic of low-voltage alternating current (AC) arc faults
文章来源:SKLFS  作者:SKLFS  发布时间:2024-05-23

Experimental research on the thermal characteristic of low-voltage alternating current (AC) arc faults

Author:Ge, F. L., Qiu, T. T., Zhang, M. S., Ji, J.

Journal:Fire Safety Journal

DOI:  10.1016/j.firesaf.2022.103732

KeywordsElectrical fires, Arc faults, Low-voltage circuit, Thermal characteristic, PVC coated wire, circuit, Engineering, Materials Science

Abstract

The objective of this paper is to study the thermal characteristic of low-voltage alternating current (AC) arc faults. Two series of experiments were designed, including polyvinyl chloride (PVC) wire ignitions experiments and electrode arcing experiments (non-ignitions) subjected to arc faults at different effective currents. The ignition time of the wire and the temperature of the electrode were investigated to characterize the arcing hazard. Results show that the ignition time of the wire decreases with the increasing arc current, and the wire with a larger cross-section area requires more time to be ignited at the same current. For non-ignition experi- ments, the electrode temperature increases first and then varies little. A heat equilibrium stage can be reached, where the heat transfer of the arc to the electrode is equal to the heat dissipation of the electrode. Furthermore, a heat transfer model for the arc fault is established to obtain the electrode temperature. The temperature of the arc-electrode interface is used to characterize the arc energy, and it is found the temperature showed a loga- rithmic increase with the current. The results of this study may be useful in the safety design of electrical wires, and can be exploited as hazard indicators for the risk assessment of electrical fires.


 
 
相关链接
Experimental research on the thermal characteristic of low-voltage alternating current (AC) arc faults
联系我们
安徽省合肥市金寨路96号
图书馆VIP
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.tsg211.com
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号